NORD Drivesystems BU0280 User Manual

Page 61

Advertising
background image

5 Parameterisation

BU 0280 GB

Subject to technical amendments

61

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P176

... [-01]

...

...

[-17]

Process data bus In

-32768 ... 32767

{ 0 }

Bus data received from DeviceNet master

… [-01] = Bus module outputs
… [-02] = Control word FI 1
… [-03] = Setpoint 1 for FI 1
… [-04] = Setpoint 2 for FI 1
… [-05] = Setpoint 3 for FI 1
… [-06] = Control word FI 2
… [-07] = Setpoint 1 for FI 2
… [-08] = Setpoint 2 for FI 2

… [-09] = Setpoint 3 for FI 2
… [-10] = Control word FI 3
… [-11] = Setpoint 1 for FI 3
… [-12] = Setpoint 2 for FI 3
… [-13] = Setpoint 3 for FI 3
… [-14] = Control word FI 4
… [-15] = Setpoint 1 for FI 4
… [-16] = Setpoint 2 for FI 4
… [-17] = Setpoint 3 for FI 4

P177

... [-01]

...

...

[-17]

Process data bus Out

-32768 ... 32767

{ 0 }

Bus data sent to DeviceNet master

… [-01] = Bus module inputs
… [-02] = Status word FI 1
… [-03] = Actual value 1 for FI 1
… [-04] = Actual value 2 for FI 1
… [-05] = Actual value 3 for FI 1
… [-06] = Status word FI 2
… [-07] = Actual value 1 for FI 2
… [-08] = Actual value 2 for FI 2
… [-09] = Actual value 3 for FI 2

… [-10] = Status word FI 3
… [-11] = Actual value 1 for FI 3
… [-12] = Actual value 2 for FI 3
… [-13] = Actual value 3 for FI 3
… [-14] = Status word FI 4
… [-15] = Actual value 1 for FI 4
… [-16] = Actual value 2 for FI 4
… [-17] = Actual value 3 for FI 4


Note X1 = This bit is active if the address of the bus module has been doubly assigned or the baud rate has
not been set correctly.