Supplementary Manual DeviceNet for NORDAC SK 200E

60

Subject to technical amendments

BU 0280 GB

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P173 Module

status

0 ... FFFF (hex)

{ 0000 }

Possible values:
Bit 0 = Bus status “Online / Not connected”
Bit 1 = Bus status “Online / Connected”
Bit 2 = Timeout (DeviceNet monitoring or time in P151)
Bit 3 = Faulty DIP setting

X1

Bit 4 = DeviceNet

“ BUS WARNING”

Bit 5 = DeviceNet

“ BUS OFF”

Bit 6 = System bus

“ BUS WARNING”

Bit 7 = System bus “BUS OFF” Bit 8 = Status FI1
Bit 9 = Status FI 1
Bit 10= Status FI 2
Bit 11= Status FI 2
Bit 12= Status FI 3
Bit 13= Status FI 3
Bit 14= Status FI 4
Bit 15= Status FI 4


Status for FI x:

Bit High

Bit Low Status

0

0

FI is offline

0

1

Unknown

FI

1

0

FI is online

1

1

FI lost or switched off

P174 Digital

inputs

0 ... 15

{ 0 }

Instantaneous view of input level logic.

Possible values:
Bit 0= Input 1 (DIN1)
Bit 1= Input 2 (DIN2)
Bit 2= Input 3 (DIN3)
Bit 3= Input 4 (DIN4)

P175 Digital

outputs

0 ... 3

{ 0 }

Instantaneous view of output level logic.

Possible values:
Bit 1= Output 1 (DO1)
Bit 2= Output 2 (DO2)