Configuration example
A DeviceNet subscriber SK TU4-DEV is connected to an SK 200E series frequency inverter via a BUS
connection unit SK TI4-TU-BUS. The field bus address (DeviceNet address) should be “14” and a baud rate of
250kBaud should be selected. The system bus only includes the frequency inverter and the DeviceNet
module. The termination resistor for the system bus is to be set at the frequency inverter. The DIP switches on
the DeviceNet module must be set as follows:

Range

Significance

DIP-Switch

ON - OFF

Configuration

example

Address

ing

Address-Bit 5

2

5

0

Address-Bit 4

2

4

0

Address-Bit 3

2

3

8

Address-Bit 2

2

2

4

Address-Bit 1

2

1

2

Address-Bit 0

2

0

0

Example address:

14

Baud

rate

Baud rate Bit 1

2

1

0

Baud rate Bit 0

2

0

1

Baud rate

1 = 250kBaud

BUS

termination

No significance

Always OFF

No significance

Always OFF

System bus

-

OFF