NORD Drivesystems BU0280 User Manual

Page 25

Advertising
background image

2 Assembly and installation

BU 0280 GB

Subject to technical amendments

25

Terminal/

Designation

Function
[factory setting]

Data

Description / wiring suggestion

Parameter

25 DIN2

Digital input 2
[I/O DeviceNet DIN2]

Low 0V ... 5V
High 15V ... 30V
R

i

= 8.1k

Input capacitance 10nF

Scan rate 1 ms
Inputs as per EN 61131-2
Type 1

Each digital input has a reaction
time of 1ms.

P174

26 DIN4

Digital input 4
[I/O DeviceNet DIN4]

P174

27 GND

28

Reference potential
for digital signals

External supply voltage for system
bus and digital inputs (DIN1 to
DIN4)

-

29 24V

30

External 24V supply

As for terminal 11

-

Potential isolation

31 24V

o

External 24V supply
for the DOs

24VDC -/+20%
Up to 1A, according to
load

reverse polarity protected

External supply voltage for digital
outputs (DO1 and DO2)
If necessary, bridge to 24V terminal

-

32 GND

o

Reference potential
for digital signals

External supply voltage for digital
outputs (DO1 and DO2)
If necessary, bridge to GND
terminal

-

33 DO1

Digital output 1
[I/O DeviceNet DO1]

Low = 0V
High: 24V
Rated current: 500mA
each

The digital outputs should be used
with a separate 24V supply

P150
P175

34 DO2

Digital output 2
[I/O DeviceNet DO2]

P150
P175

35 GND

o


36

Reference potential
for digital signals

External supply voltage for digital
outputs (DO1 and DO2)
If necessary, bridge to GND
terminal

-



Details of M12 connections of the SK TU4-DEV-M12
The special wiring of the M12 round plug connector
enables the connection of both single and double
sensors, which are equipped with normal M12 system
connectors in the standard sensor/actuator
configuration.

With the use of M12 round plug connectors, the terminal
bar connectors for the digital inputs (Terminals 19, 20,
25, 26) must not be used.

Advertising