Supplementary Manual DeviceNet for NORDAC SK 200E

64

Subject to technical amendments

BU 0280 GB

6.2 Error messages

6.2.1

Table of possible error messages (caused by the bus) in the frequency inverter

The following error messages concern bus-related messages which are indicated on the frequency inverter. A
complete list of error messages for the frequency inverter (SK 200E) can be found in the relevant manual
(BU0200).

Display in the
SimpleBox

Fault

Text in the ParameterBox

Cause

Remedy

Group

Details in
P700 / P701

E010

10.2

External bus module
telegram timeout

(Timeout of DeviceNet Bus
Watchdog)

Telegram transfer is faulty.

Check external connection.

Check bus protocol program process.

Check Bus master.

10.3

Timeout via (P151)

Telegram transfer is faulty.

Check watchdog time (P151)

Check external connection.

Check bus protocol program process.

Check Bus master.

Control word is invalid (Bit 10 = 0)

10.9

Module not found

The module entered in parameter (P120) is not available.