6 Error monitoring and error messages

BU 0280 GB

Subject to technical amendments

65

6.2.2

Table of possible error messages in the bus module

The following error messages concern bus-related messages, which are indicated on the DeviceNet module
(SK CU4DEV or SK TU4DEV(-

…)).

Display

in the SimpleBox

Fault

Text in the ParameterBox

Cause

Remedy

Group

Details in
P170

E1000

1000 EEPROM

error

Module faulty

1010

System bus 24V missing

Check connections and supply cables

Ensure 24V voltage supply

1020

System bus timeout

Check time set in parameter (P151).

Telegram transfer is faulty.

Check external connection.

Check bus protocol program process.

Check Bus master

1030

System bus OFF

Check connections and supply cables

Ensure 24V voltage supply

Check Bus master

5210

DeviceNet Bus OFF

5211

Address already allocated

Avoid double assignment of addresses

Comply with address range 1 ... 63

Match master addressing to option addressing

5212 Illegal

baud

rate

Invalid setting on DIP switch

5220 DeviceNet

Timeout