2-11 o.c.(over current) error – Sunlight Supply Samsung Programmable Thermostat for Split Systems User Manual

Page 107

Advertising
background image

Samsung Electronics 12-44

12-2-11

O.C.(Over Current) error

1.

Checklist

:

1) Is the refrigerant charged properly?

2) Does the compressor rotate normally?(Reverse rotation, Locking etc.)

3) Is connection of compressor wire normal?

4) Is compressor motor normal?(Insulation, Coil resistance etc.)

5) Does a temporary cycle overload condition happened?

2.

Troubleshooting

procedure

Yes

Yes

No

No

No

No

No

No

Yes

Yes

Yes

Does the compressor wire connected to the

compressor normally?

Yes

Yes

Exchange the compressor

Reinstall and remove the obstruction

Is the installation of outdoor unit good?

Reinstall and remove the obstruction

Is the installation of indoor unit good?

Open valve screw to the end.

Are the service valves full opened?

Correct the compressor wire connection

Is insuration resistance between each

compressor terminal and body normal?

Exchange INVERTER PCB

No

Does the compressor rotate normally?

Did AC power voltage interruption happen

during the compressor in operation?

Exchange the compressor

Check AC power source