2-4 total current trip error – Sunlight Supply Samsung Programmable Thermostat for Split Systems User Manual

Page 99

Advertising
background image

Samsung Electronics

12-36

12-2-4 Total current trip error

1.

Checklist

:

1) Is the input power voltage proper?

2) Is the refrigerant charged properly?

3) Does the compressor rotate normally?(Reverse rotation, Locking etc.)

4) Does the outdoor fan operate normally?(Fan propeller loss, Motor error ect.)

5) Is the installation condition of outdoor unit good?(Piping, Space etc.)

6) Is there no ventilation obstruction at the surrounding of outdoor unit?(Outdoor unit cover, Fan front obstruction etc.)

7) Is there no ventilation obstruction at the surrounding of indoor unit?(Overload condition in heating mode)

2.

Troubleshooting

procedure

No

Yes

Yes

Are the service valves full opened?

Yes

Yes

Check AC power source

No

No

Reinstall and remove the obstruction

Is the installation of outdoor unit good?

Reinstall and remove the obstruction

No

Is the installation of indoor unit good?

Exchange the compressor

No

Does the compressor rotate normally?

Open valve screw to the end.

Is AC power voltage normal during the

compressor in operation?

Exchange INVERTER PCB

Yes