Compressor wire missing error/rotation error

Indoor display

ل

Outdoor error

Outdoor display

م

ل

م

Compressor wire missing error/rotation
error

1.Checklist :
1) Is the connection of cable for the compressor?
2) Is the compressor wire is connected clockwise? U(RED)-V(BLU)-W(YEL)
3) Is the interphase resistance of compressor normal?

2. Troubleshooting procedure

Is the restart error occurred again?

Terminate the service

NO

YES

Is the connec

Ɵon of compressor

wire is normal? (PBA and

Compressor)

YES

Is the compressor body and

interphase resistance insulated?

NO

Exchange the Outdoor PBA

Connect the comp wire normally

YES

NO

Exchange the compressor

Is the restart error occurred again?

Terminate the service

NO

YES

Restart a

Ōer power oī.