DC_link voltage sensor error

Indoor display

ل

Outdoor error

Outdoor display

م

DC_link voltage sensor error

1.Checklist :
1) Is the input voltage of outdoor terminal block is normal?
2) Is the reactor wire connected?
3) Is the DC_link capacitor(A*V18***:CE101,CE102,CE103,A*V24***:CE001,CE002,CE003,CE004)) assembled in accordance
the specification? (Outdoor PBA)
4) Is the DC_link resistor(A*V18***:R104,R106,R107,R108,A*V24***:R004,R005,R006,R007) value is normal? (Outdoor PBA)

2. Troubleshooting procedure

Is the connected of reactor wire?

(PBA-Reactor)

Is the DC_link sensing voltage(R104

or R004) is normal in opera

Ɵonmode?

Normal range (0.2Vdc~2.8Vdc)

YES

Exchange the Outdoor PBA

NO

Is the DC_link voltage (CE101 or

CE001) is normal in opera

Ɵonmode?

Normal range(280Vdc~320Vdc)

Check the power input

NO

YES

YES

Connect the reactor wire

NO

Restart a

Ōer power oī.

Start the opera

Ɵon (cooling mode or heaƟng mode)

Exchange the Reactor

Is the reactor insula

Ɵon damaged?

YES

Exchange the Outdoor PBA

NO