Sunlight Supply Samsung Programmable Thermostat for Split Systems User Manual

Page 74

Advertising
background image

12-

7

Indoor fan motor speed detecting error (BLDC fan)

Indoor display

ل

ل

Indoor fan error

1.Checklist :
1) Is the indoor units fan motor properly connected with the connector(CN72)?
2) Is the AC voltage correct?

2. Troubleshooting procedure

Does the fan rotate?

Power o

ī and Separate the Fan motor wire from

CN72 on Indoor PBA

NO

YES

Is the fan error appeared again?

Reassemble the fan wire and input the power again

YES

Is the voltage of CN72 #3-#5 and

#3-#6 with in 1Vdc~15Vdc during

the opera

Ɵon?

YES

Exchange the Indoor PBA

Terminate the
service

NO

NO

PBA problem or Motor problem

Change the PBA

Įrst and check the operaƟon

Exchange the Fan motor

Is there short among each pin

#1~#6

YES

Exchange the Fan
motor

Is the voltage of CN72 #1-#3 over

250Vdc

NO

Follow the check procedure of Indoor unit power
supply error check

NO

YES

Restart a

Ōer power oī.

Advertising