2-3 the outdoor unit fan error – Sunlight Supply Samsung Programmable Thermostat for Split Systems User Manual

Page 98

Advertising
background image

12-35

Samsung Electronics

12-2-3

The Outdoor unit Fan error

1.

Checklist:

1) Are the input power voltage and power connection correct?

2) Is the motor wire connected to the outdoor PCB correctly?

3) Is there no obstacle at the surrounding of motor and propeller?

4) Does the driver in the motor case broken?

2. Troubleshooting

procedure

# TEST operation #
press K900 button on the
MAIN PCB after power on.

- once : cooling mode
- twice in a second :

heating mode

Exchange INVERTER PCB

Exchange INVERTER PCB

No

Yes

Yes

Yes

No

Check the connection of CN40 and CN41

Is the connection of FAN housing certainly to

PCB socket?(CN40, CN41)

Exchange the FAN motor because of driver

inside of the motor case broken

No

Take off each Fan motor housing after 1 minutes

from turning off the power

Follow the check procedure of

outdoor unit power supply error check

No

Is each resistance of FAN cable housing

pin #1-#3 over 1Mohm, pin #4-#3, #5-#3 and

#6-#3 over 1Kohm on each FAN motor?

Mount each Fan housing to PCB socket and

turn on the power

Exchange INVERTER PCB

No

Is the Pin voltage #1 - #3 of CN40 and 41

over 250V?

Exchange the FAN motor not in rotation

No

Exchange INVERTER PCB

Yes

Exchange the FAN motor

No

Yes

Yes

Yes

No

Is the Pin voltage #5 - #3 of CN40 and 41 15V?

Is the Pin voltage #5 - #3 of CN40 and 41

within 1-6V during the operation?

Is the Fan in rotation during

TEST operation in cooling mode

Is the Pin voltage #6 - #3 of CN40 and 41

changed high(4-5V) and low(0-1V) in case of

making manual rotation slowly?

Is the Pin voltage #7 - #3 of CN40 and

41 low(0-1V) in normal rotation?

Yes