2-14 compressor lock error – Sunlight Supply Samsung Programmable Thermostat for Split Systems User Manual

Page 110

Advertising
background image

12-47

Samsung Electronics

12-2-14 Compressor lock error

1. Checklist

:

1) Is the connection of cable for the compressor and power?

2) Is the interphase resistance of compressor normal?

2. Troubleshooting

procedure

Yes

Restart after power off.

Is the lock error occurred again?

Is the interphase resistance value of

compressor(u

lv, vlw, wlu) normal?

Is the connection cable for the

compressor and power terminal normal?

Exchange the PCB.

Terminate the service.

Exchange the compressor.

Is the compressor body and

interphase resistance insulated?

Exchange the compressor.

Correct the cable connection.

Yes

Yes

Yes

No

No

No

No