DC_link voltage under/over error, Over voltage protection error/PFC over load

Indoor display

ل

Outdoor error

Outdoor display

ل

م

DC_link voltage under/over error
Over voltage protection error
PFC over load

1.Checklist :
1) Is the input voltage of outdoor terminal block is normal?
2) Is the input voltage is higher than 300Vac?
3) Is the reactor wire connected?
3) Is the DC_link capacitor(A*V18***:CE101,CE102,CE103,A*V24***:CE001,CE002,CE003,CE004)) assembled in accordance
the specification? (Outdoor PBA)

4) Is the DC_link resistor(A*V18***:R104,R106,R107,R108,A*V24***:R004,R005,R006,R007) value is normal? (Outdoor PBA)
2. Troubleshooting procedure

Is the connected of reactor wire?

(PBA-Reactor)

Is the DC_link sensing voltage(R104

or R004) is normal in opera

Ɵon mode?

Normal range (0.2Vdc~2.8Vdc)

YES

Exchange the Outdoor PBA

NO

Is the DC_link voltage (CE101 or

CE001) is normal in opera

Ɵonmode?

Normal range(280Vdc~320Vdc)

Check the input power

NO

YES

YES

Connect the reactor wire

NO

Restart a

Ōer power oī.

Is the the input voltage is nomal?

Normal range(180Vac ~ 270Vac)

Restart a

Ōer power oī.

Start the opera

Ɵon (cooling mode or heaƟng mode)

Check the input power in the powercord.

NO

YES

Exchange the Reactor

Is the reactor insula

Ɵon damaged?

NO

Exchange the Outdoor PBA

YES