I_trip error, PFC over current

Indoor display

ل

Outdoor error

Outdoor display

م

م

I_trip error, PFC over current

1.Checklist :
1) Is the PFC Shunt(A*V18***:R062,R063,A*V24***:R807,R808,R809) resistance value correct? Check the resistor is opened
2) Is the condition of surrounding temperature abnormal overload?
3) Is there any problem as like the temperature sensor separation or measurement value error?
4) Is the interphase resistance of compressor normal?

2. Troubleshooting procedure

Is the condi

Ɵon of indoor/outdoor

temperature normal load?

Restart a

Ōer returning to the normal load

YES

YES

Is the connec

Ɵon cable for the

compressor and power terminal

normal?

YES

Correct the cable connec

Ɵon

Is the I_trip error
occurred again?

NO

NO

Exchange the Outdoor PBA

Is the posi

Ɵon of temperature

sensor and the sensing value

normal?

Correct the sensor posi

Ɵon or exchange the sensor

NO

YES

Restart a

Ōer power oī.

Terminate the
service

NO