Fault Diagnosis by Symptom

12-2-1 No Power(completely dead) - Initial diagnosis

1.

Checklist:

1) Is Power source voltage normal?

2) Is AC power linked correctly?( miss-wiring, wire detaching etc. )

3) Is any LED on the MAIN PCB of Outdoor unit lit?

4) Is terminal voltage for indoor unit normal?(230Vac nominal)

5) Is Wired remote controller installed correctly?

2.

Troubleshooting

procedure

Check AC power source.

Reconnect wires correctly

Abnormal

Check outdoor unit terminal

block voltage on each N-R,N-S,N-T

(230Vac nominal)

Turn off the breaker and turn it on after 30 seconds

Check the setting temperature

Check Inner wiring of outdoor unit

Abnormal

Check outdoor unit terminal

block voltage on L-N for indoor unit

(230Vac nominal)

Check cable and connection of wire between

indoor and outdoor unit

Abnormal

Check indoor unit

terminal block voltage on L-N

(230Vac nominal)

Check Indoor control

PCB, Transformer, and FUSE on PCB and

replace one which is broken.

Abnormal

Check indoor unit

terminal block voltage on V1-V2

(12Vdc nominal)

Check cable and connection of wire between

remote controller and indoor unit

Abnormal

Check DC power voltage of

remote controller(V1,V2)

Replace wired remote controller

No display

Press the On/Off button on the

wired remote controller to operate the air

conditioner

Set DIP SW correctly

Wrong setting

Check DIP SW in the

wired remote controller.

Check each item according to error code list

Yes

Is there any error display on

the wired remote controller