Lenze · E94AYCDN communication module (DeviceNet™) · Communication Manual · DMS 5.0 EN · 02/2014 · TD17
23
5
Installation
5.2
Electrical installation
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
[5-3]
DeviceNet line
E94YCDN008
D1 ... n: Devices 1 ... n
S: scanner (e.g. PLC, IPC)
Note!
• Connect a bus terminating resistor of 120 each to the first and the last node of the
DeviceNet line.
• Connect the shield at the voltage supply together with the "V-" connection to GND
once. For this purpose, use the centre point of the DeviceNet line, if possible.
• Connect the shield of the DeviceNet cable for each node only to the SHIELD
connection of the plug connector.