4 bus cable length, Bus cable length, 5installation – Lenze E94AYCDN User Manual
Page 28
![background image](/manuals/565807/28/background.png)
5
Installation
5.2
Electrical installation
28
Lenze · E94AYCDN communication module (DeviceNet™) · Communication Manual · DMS 5.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.2.4
Bus cable length
The following bus cable lengths are possible depending on the baud rate and the cable type used
(thick cable/thin cable):
If both thick and thin cables are used, the maximum cable lengths depending on the baud rate can
be determined as follows:
Baud rate [kbps]
Bus cable lengths [m]
Thick cable
Thin cable
125
500
250
250
100
500
100
Baud rate [kbps]
Max. bus cable length
125
500 m = L
thick
+ 5 L
thin
250
250 m = L
thick
+ 2.5 L
thin
500
100 m = L
thick
+ L
thin
L
thick
: Length of the thick cable
L
thin
: Length of the thin cable
Note!
Select the baud rate which depends on the data volume, cycle time, and number of
nodes just high enough to suit your application.