Devicenet: internal mapping error [0x00c86110, Devicenet: invalid parameter set [0x00c8641f, Devicenet: error: lenze setting loaded [0x00c86420 – Lenze E94AYCDN User Manual

Page 45: Devicenet: idle mode [0x00c88132, Devicenet: timeout i/o connection [0x00c88111, Devicenet: explicit message timeout [0x00c88112, 0x00c86110, 0x00c8641f, 0x00c86420, 0x00c88111

Advertising
background image

Lenze · E94AYCDN communication module (DeviceNet™) · Communication Manual · DMS 5.0 EN · 02/2014 · TD17

45

10

Error messages

10.2

Possible causes and remedies

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

DeviceNet: Internal mapping error [0x00c86110]

DeviceNet: Invalid parameter set [0x00c8641f]

DeviceNet: Error: Lenze setting loaded [0x00c86420]

DeviceNet: Idle mode [0x00c88132]

DeviceNet: Timeout I/O Connection [0x00c88111]

DeviceNet: Explicit Message Timeout [0x00c88112]

Response (Lenze setting printed in bold)

Setting: not possible

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

More than 64 bytes have been mapped

Carry out

Configuring I/O data (PDO mapping) ( 36)

again.

Response (Lenze setting printed in bold)

Setting: not possible

None  system fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

No active parameter set could be loaded.

Download application again (including module).

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Access to parameter set in memory module via standard

device was not successful.

Download application again (including module).

Response (Lenze setting printed in bold)

Setting:

C13880/1

/

C14880/1

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble Warning locked  Warning  Information

Cause

Remedy

The host (PLC, scanner) is in the "Program" mode (RUN bit

in the Scanner Command Register has not been set).

Set the host (PLC, scanner) to "Run" mode.

Response (Lenze setting printed in bold)

Setting:

C13880/2

/

C14880/2

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble Warning locked  Warning  Information

Cause

Remedy

Timeout of the poll or CoS/Cyclic I/O connection

Check the Expected Packet Rate in class 5, instance 2 (Poll

I/O)/instance 4 (CoS/Cyclic I/O), attribute 9

Response (Lenze setting printed in bold)

Setting: not possible

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Time-out of the Explicit Message connection

Check the Expected Packet Rate in class 5, instance 1

(Explicit Message), attribute 9

Advertising