3 specification of the bus cable, Specification of the bus cable, 5installation – Lenze E94AYCDN User Manual

Page 25

Advertising
background image

Lenze · E94AYCDN communication module (DeviceNet™) · Communication Manual · DMS 5.0 EN · 02/2014 · TD17

25

5

Installation

5.2

Electrical installation

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.2.3

Specification of the bus cable

The nodes of the bus system must be wired with a fieldbus cable - a DeviceNet thick or thin cable -

according to the DeviceNet specifications (DeviceNet Adaption of CIP, Edition 1.1, Volume 3).

DeviceNet thick and thin cables for instance are manufactured by Belden Inc., Lapp, C&M Corp., and

Madison Cable Corp.

Properties of the thick cable according to the DeviceNet specifications

Note!

If you do not wish to use a thick or thin cable, the cable used must meet the requirements

given in the DeviceNet specifications.
A cable that does not meet the requirements given in the DeviceNet specifications must

not be used!

General properties
Arrangement

Two shielded, symmetrical cables, common axis with drain wire in the centre

Overall shielding

Coverage: 65 percent

AWG 36, or at least 0.12 mm tinned copper braid (individually tinned)

Drain wire

At least copper 18; at least 19 cores (individually tinned)

Outer diameter

10.41 mm (min.) ... 12.45 mm (max.)

Roundness

A radius deviation must not exceed 15 percent of one half of the outer

diameter

Cable sheath labelling

Vendor name, part number and additional labelling

DC resistor specification (braid,

wrapping, discharge)

5.74 /km (nominally up to 20°C)

Certifications (U.S. and Canada)

NEC (UL), CL2/CL3 (minimum)

Bend radius

20 x the diameter (installation) / 7 x the diameter (fixed)

Ambient temperature during

operation

-20 ... +60°C at 8 A; linear current derating to zero at 80°C

Storage temperature

-40 ... +85°C

Pull tension

max. 845.5 N