C14861 | module state, C14862 | network status, C14863 | baud rate – Lenze E94AYCDN User Manual

Page 60: C14861, C14862, C14863, 11 parameter reference

Advertising
background image

11

Parameter reference

11.3

Parameters of the communication module for the MXI2 slot

60

Lenze · E94AYCDN communication module (DeviceNet™) · Communication Manual · DMS 5.0 EN · 02/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C14861

C14862

C14863

Parameter | Name:

C14861 | Module state

Data type: UNSIGNED_16

Index: 9714 = 0x25F2

Display of the current module state
Selection list

(read only)

Info

0 Nonexistent

No online value available (communication module is

offline).

1 Device Self Test

The communication module is currently undergoing a

self-test.

2 Device Operational

The communication module is working perfectly.

3 Device in Standby

The communication module has not been completely

configured yet or the configuration is incorrect.

4 Minor Fault

The communication module has a fault that can be

rectified.

5 Unrecoverable Fault

The communication module is defective and must be

replaced.

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14862 | Network status

Data type: UNSIGNED_16

Index: 9713 = 0x25F1

Display of the current network status of the DeviceNet node
Selection list

(read only)

Info

0 Nonexistent

No online value available (communication module is

offline).

1 Not online

• The communication module is not supplied with

voltage via DeviceNet.

• The Duplicate MAC ID test has not been completed

yet.

2 Link OK

The communication module is working perfectly and has

established a connection to the scanner.

3 Online / Not connected

The communication module

• is working correctly;

• has performed the Duplicate MAC ID test;

• has not been connected to the scanner yet.

4 Minor Fault

The communication module has a fault that can be

rectified.

5 Critical Link Failure

The communication module cannot access the fieldbus

(e.g. Duplicate MAC ID, Bus Off, invalid baud rate etc.).

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14863 | Baud rate

Data type: UNSIGNED_8

Index: 9712 = 0x25F0

Display of the baud rate
Selection list

(read only)

0 125.00 kbps
1 250.00 kbps
2 500.00 kbps

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Advertising