Lenze · E94AYCDN communication module (DeviceNet™) · Communication Manual · DMS 5.0 EN · 02/2014 · TD17

31

6

Commissioning

6.2

Configuring the host (PLC, scanner)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.2

Configuring the host (PLC, scanner)

For communication with the communication module, the host (PLC, scanner) must be configured

first.

Configuration for device control
For the configuration of DeviceNet, the EDS file of the communication module has to be imported

via the configuration software (e.g. »RSNetWorx« Rockwell software).
The EDS file E94AYCDN_Vxxx.eds required for configuration can be found in the download area at:

www.lenze.com

Specifying the user data length

The Servo Drives 9400 support the configuration of max. 32 process data words (max. 64 bytes) per

direction.
The user data length for consumed and produced I/O data can vary.
The user data lengths (number of process data) must be set and stored via the »Engineer« or the

scanner (

Lenze Class (0x66 / 102)

( 75)

):

Note!

The direction of the flow of information must be observed!

• Consumed I/O data: process data from the scanner to the drive (device)
• Produced I/O data: process data from the drive (device) to the scanner

User data length for consumed I/O data

User data length for produced I/O data

Setting via the »Engineer« using

C13883

/

C14883

Setting via the »Engineer« using

C13884

/

C14884

The length of the ports mapped into the receipt PDO

results from the

Configuring I/O data (PDO mapping)

( 36)

and is displayed in

C13854/1

/

C14854/1

. If this

length does not correspond to the user length data of the

consumed I/O data from

C13883

/

C14883

, the

DeviceNet: Consumed I/O data length is contradictory

[0x00C88211] ( 46)

error message will be generated

and entered as a warning in the logbook of the standard

device when the I/O connection is established.

The length of the ports mapped into the transmission

PDO results from the

Configuring I/O data (PDO

mapping) ( 36)

and is displayed in

C13855/1

/

C14855/1

. If this length does not correspond to the user

length data of the produced I/O data from

C13884

/

C14884

, the

DeviceNet: Produced I/O data length is

contradictory [0x00C88212] ( 46)

error message will

be generated and entered as a warning in the logbook of

the standard device when the I/O connection is

established.