3 possible settings via dip switch, 1 setting the station address (mac id), 2 setting the baud rate – Lenze E94AYCDN User Manual

Page 32: Possible settings via dip switch, Setting the station address (mac id), Setting the baud rate, 6commissioning

Advertising
background image

6

Commissioning

6.3

Possible settings via DIP switch

32

Lenze · E94AYCDN communication module (DeviceNet™) · Communication Manual · DMS 5.0 EN · 02/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.3

Possible settings via DIP switch

[6-1]

DIP switch

6.3.1

Setting the station address (MAC ID)

• The station address is set via the switches 1 ... 32 (MAC ID).
• The housing labelling corresponds to the binary values of the individual switches for

determining the station address.

• Valid address range: 0 … 63
• The current address setting is displayed in

C13864

/

C14864

.

Example: Setting of station address 23

DIP switch positions for setting the station address

( 83)

6.3.2

Setting the baud rate

The baud rate is set via the switches 1 and 2 (Baud).

The current baud rate setting is displayed in

C13863

/

C14863

.

E94YCPM001D

The following can be set via the DIP switch on the front:

• Station address

Range: MAC ID

Switches: 1 ... 32

• Baud rate

Range: Baud

Switches: 1 and 2

Lenze setting: all switches OFF

Switch (MAC ID)

32

16

8

4

2

1

Switch status

OFF

ON

OFF

ON

ON

ON

Value

0

16

0

4

2

1

Station address

= sum of the values = 16 + 4 + 2 + 1 = 23

Switch (Baud)

Baud rate

2

1

OFF

OFF

125 kbps

OFF

ON

250 kbps

ON

OFF

500 kbps

ON

ON

No function / switch status is not supported.