DeviceNet: Communication error [0x00c88121]

DeviceNet: Online [0x00c88141]

DeviceNet: Consumed I/O data length is contradictory [0x00C88211]

DeviceNet: Produced I/O data length is contradictory [0x00C88212]

Response (Lenze setting printed in bold)

Setting:

C13880/3

/

C14880/3

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble Warning locked  Warning  Information

Cause

Remedy

A communication error occurred

Check cables and terminals.

Response (Lenze setting printed in bold)

Setting: not possible

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The DeviceNet is online

-

Response (Lenze setting printed in bold)

Setting: not possible

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The number of consumed I/O data via DeviceNet does

not correspond to the number configured by the

standard device through port mapping (displayed in

C13854/1

/

C14854/1

)

Check whether the differing data length is sufficient for

the application. If required, adapt the port mapping or

the data length of the I/O data consumed via

C13883

/

C14883

).

Response (Lenze setting printed in bold)

Setting: not possible

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The number of produced I/O data via DeviceNet does not

correspond to the number configured by the standard

device through port mapping (displayed in

C13855/1

/

C14855/1

)

Check whether the differing data length is sufficient for

the application. If required, adapt the port mapping or

the data length of the I/O data produced via

C13884

/

C14884

).