2 devicenet connection, Devicenet connection, Devicenet connection ( 24) – Lenze E94AYCDN User Manual

Page 24: 5installation

Advertising
background image

5

Installation

5.2

Electrical installation

24

Lenze · E94AYCDN communication module (DeviceNet™) · Communication Manual · DMS 5.0 EN · 02/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.2.2

DeviceNet connection

The bus connection of the communication module is effected via the 5-pole plug connector with

double screw connection (X225).

[5-4]

5-pole plug connector with double screw connection

Plug connector assignment (X225)

Internal wiring of the plug connector (X225)

[5-5]

Internal wiring X225

E94YCDN001C

Terminal

Cable colour

Description

V+

red

External voltage supply

• U = 24 V DC

• I

max

= 170 mA

CAN_H

White

Data line / input for bus terminating resistor (120 )

SHIELD

Shielding

CAN_L

Blue

Data line / input for bus terminating resistor (120 )

V-

Black

Reference potential for external voltage supply

E94YCDN006

V

cc

V

cc

V+

CAN_H

SHIELD

CAN_L

V-

7

6

2

8

5

3

1

4

Advertising