C00637 | resp. to new module in mxi2, C01501 | resp. to comm. error with mxi1, C01502 | resp. to comm. error with mxi2 – Lenze E94AYCDN User Manual

Page 49: 11 parameter reference

Advertising
background image

Lenze · E94AYCDN communication module (DeviceNet™) · Communication Manual · DMS 5.0 EN · 02/2014 · TD17

49

11

Parameter reference

11.1

Communication-relevant parameters of the standard device

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00637

C01501

C01502

Parameter | Name:

C00637 | Resp. to new module in MXI2

Data type: UNSIGNED_32

Index: 23939 = 0x5D83

Response for the case where a new module has been plugged into slot 2 of the standard device.
Selection list

(Lenze setting printed in bold)

1 Fault
6 Information
5 Warning
4 Warning Locked
3 Quick stop by trouble
0 No Response

Read access  Write access  CINH  PLC-STOP  No transfer

Parameter | Name:

C01501 | Resp. to comm. error with MXI1

Data type: UNSIGNED_32

Index: 23074 = 0x5A22

Response to a communication error between an "intelligent" module in slot 1 and the standard device
Selection list

(Lenze setting printed in bold)

0 No Response
1 Fault
3 Quick stop by trouble
4 Warning Locked
5 Warning

Read access  Write access  CINH  PLC-STOP  No transfer

Parameter | Name:

C01502 | Resp. to comm. error with MXI2

Data type: UNSIGNED_32

Index: 23074 = 0x5A22

Response to a communication error between an "intelligent" module in slot 2 and the standard device
Selection list

(Lenze setting printed in bold)

0 No Response
1 Fault
3 Quick stop by trouble
4 Warning Locked
5 Warning

Read access  Write access  CINH  PLC-STOP  No transfer