1 writing integer codes, 12 implemented devicenet objects – Lenze E94AYCDN User Manual
Page 79
Lenze · E94AYCDN communication module (DeviceNet™) · Communication Manual · DMS 5.0 EN · 02/2014 · TD17
79
12
Implemented DeviceNet objects
12.11
Examples for reading/writing with the »Class Instance Editor«
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12.11
Examples for reading/writing with the »Class Instance Editor«
The »Class Instance Editor« is a function of the Rockwell software »RSNetWorx«.
12.11.1
Writing integer codes
The maximum speed (n
max
) is to be set to 4500 rpm using code C00011.
Enter the following in the input fields of the »Class Instance Editor« (fig.
):
• Description: Set Single Attribute (write code)
• Class: 6E (access to Lenze code)
• Instance: B (hex value of the code)
• Attribute: 1 (hex value of the subcode)
• ”Data sent to the device”:
4500 = 4500 [min
-1
] = FD2 (speed as hex value)
• Transmit data size: Double (4 bytes)
[12-1] »Class Instance Editor«: Writing integer codes