79

12

Implemented DeviceNet objects

12.11

Examples for reading/writing with the »Class Instance Editor«

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

12.11

Examples for reading/writing with the »Class Instance Editor«

The »Class Instance Editor« is a function of the Rockwell software »RSNetWorx«.

12.11.1

Writing integer codes

The maximum speed (n

max

) is to be set to 4500 rpm using code C00011.

Enter the following in the input fields of the »Class Instance Editor« (fig.

[12-1]

):

• Description: Set Single Attribute (write code)
• Class: 6E (access to Lenze code)
• Instance: B (hex value of the code)
• Attribute: 1 (hex value of the subcode)
• ”Data sent to the device”:

4500 = 4500 [min

-1

] = FD2 (speed as hex value)

• Transmit data size: Double (4 bytes)

[12-1] »Class Instance Editor«: Writing integer codes