C14864 | active mac id, C14880 | response in the case of comm. fault, C14883 | data length of i/o data consumed – Lenze E94AYCDN User Manual

Page 61: C14883, C14864, C14880/1, C14880/2, C14880/3, 11 parameter reference

Advertising
background image

Lenze · E94AYCDN communication module (DeviceNet™) · Communication Manual · DMS 5.0 EN · 02/2014 · TD17

61

11

Parameter reference

11.3

Parameters of the communication module for the MXI2 slot

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C14864

C14880

C14883

Parameter | Name:

C14864 | Active MAC ID

Data type: UNSIGNED_8

Index: 9711 = 0x25EF

Display of the active MAC ID
Display area

(min. value | unit | max. value)

0

255

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14880 | Response in the case of comm. fault

Data type: UNSIGNED_8

Index: 9695 = 0x25DF

Monitoring response in the case of communication fault

A change in the monitoring response becomes immediately effective.
Selection list

0 No Response
1 Fault
3 Quick stop by trouble
4 Warning Locked
6 Information

Subcodes

Lenze setting

Info

C14880/1

0: No Response

Idle Mode

C14880/2

0: No Response

Timeout I/O connection

C14880/3

0: No Response

Communication error

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14883 | Data length of I/O data consumed

Data type: UNSIGNED_8

Index: 9692 = 0x25DC

Setting of the data length (in bytes) of the I/O data received by the device via DeviceNet.

Note:

• If the data length is changed, the DeviceNet scanner will be informed about this change (consumed data size).

• If the data length is reduced, it must be checked before whether the intended data length is sufficient for the

application.

• If the data length of the consumed I/O data does not correspond to the length of the mapped ports which is

specified by the drive via PDO mapping, the

DeviceNet: Consumed I/O data length is contradictory [0x00C88211]

( 46)

error message is generated and entered as a warning into the logbook of the standard device.

• If the number of consumed I/O data deviates from the Lenze setting (4 bytes), the "Automap on Add" function in

the scanner configuration dialog of the »RSNetWorx« software has to be deactivated and the number of the

process data words has to be adapted via the "Edit I/O parameters" button.

Setting range

(min. value | unit | max. value)

Lenze setting

0

64 4

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT