background image

Safety engineering

Device modules

Safety module SM300

1

1.2

1.2.3

1.2-4

EDS94AYAD EN 2.2

1.2.3.3

Elements of the module

SSP94SM317

Fig. 1.2-2

Module view

Pos.

Description

PROFIsafe target address switch (on the left housing side)

X82.1

Pluggable terminal strips for input and output signals

X82.2
X82.3
X82.4

Pos.

Colour

State

Description

MS

Green

On

Drive-based safety is initialised faultlessly.

Blinking

Drive-based safety is initialised faultlessly. Internal

communication to the standard device is not

possible.

Off

Drive-based safety is not initialised.

Acknowledgement is not possible.

EN

Yellow

On

Controller enabled

Off

Non-safe display ”STO”

ME

Red

On

System error:

z

After a serious internal error, STO is activated.

z

Can only be reset by switching the 24V supply.

Blinking

Error:

z

After an internal error or an error at the safe

inputs, a standstill function is activated.

z

The safety class is quit.

z

Acknowledgement is possible.

Flashing

Fault:

z

A monitoring function has responded and

activated a standstill function.

z

The safety class is not quit.

z

Acknowledgement is possible.

Off

Error-free operation

PS

Red

On

Error PROFIsafe:

z

Communication is not possible.

z

Acknowledgement is possible.

Blinking

No valid PROFIsafe configuration

Off

PROFIsafe is error-free.

DE

Red

On

The module is not accepted by the standard device

(see notes given in the documentation for the

standard device).

Displays