Safety engineering – Lenze E94AYAD - SM300 User Manual

Page 16

Advertising
background image

Safety engineering

Device modules

Safety module SM300

1

1.2

1.2.3

1.2-6

EDS94AYAD EN 2.2

Cable cross-sections and tightening torques
Type

[mm

2

]

[Nm]

AWG

[lb-in]

Wire end ferrule,

insulated

0.25 ... 0.5

Spring terminal

24 ... 20

Spring terminal

Rigid

0.14 ... 1.5

26 ... 16

1.2.3.4

Technical data

The inputs are isolated and designed for a low-voltage supply of 24 V DC.

Detailed features of the inputs and outputs
Signal

Specification

min.

typ.

max.

I1A, I1B

I2A, I2B

I4A, I4B

AIE

PLC input, IEC-61131-2, 24 V, type 1
LOW signal

[V]

-3

0

5

Input current

[mA]

15

HIGH signal

[V]

15

24

30

Input current

[mA]

2

15

Input capacitance

[nF]

3.3

AIE

Pulse duration

[ms]

300

10

4

CLA, CLB

PLC output, IEC-61131-2, 24 V DC, 50 mA
LOW signal output voltage

[V]

0

0.8

HIGH signal output voltage

[V]

17

24

29

Output current

[mA]

50

Width of the test pulse

[μs]

750

Test pulse rate

[s]

1.8

Cable resistance of a passive sensor

[kΩ]

2

+, -

Supply voltage of the module via a safely

separated power supply unit (SELV/PELV)

[V]

19,2

24

30

Input current

[A]

Tab. 1.2-1

Technical data

The chapter ”Response times” must be observed as well ( 1.3.5.2).

1.2.3.5

Commissioning

ƒ Settings in or at the module:

– PROFIsafe target address switch

ƒ Required settings in the basic device:

– C00214, type of safety module

ƒ Integration of the SM300 into the drive application
ƒ During commissioning and after the replacement of a module it is vital

to check the safety function.