Safety engineering

Basics

Safety instructions

1

1.1

1.1.5

1.1-4

EDS94AYAD EN 2.2

1.1.5

Safety instructions

1.1.6

Application as directed

The safety modules SMx (E94AYAx) may only be used together with Lenze

drive controllers of the L-force | 9400 (E94A...) series.
Any other use shall be deemed inappropriate!

ƒ Only skilled personnel are permitted to install and commission the

safety functions.

ƒ All control components must comply with the demands of the hazard

and risk analysis.

ƒ Install the controllers in control cabinets with IP54 protection.
ƒ Wiring with insulated wire end ferrules or rigid cable is vital.
ƒ For modules without integrated short-circuit monitoring:

– All safety-relevant external cables (e.g. control cables for safety

functions, feedback contacts) outside the control cabinet must be

protected, e.g. by a cable duct.

– In this connection, make sure that short circuits cannot occur!
– For further measures see ISO 13849-2.

ƒ If external forces act on the drive axes, additional brakes are necessary.

The effect of the gravitational force on hanging loads must be

especially observed!

Danger!

If the request for the safety function is cancelled, the drive will

restart automatically.
You must provide external measures which ensure that the drive

only restarts after a confirmation (EN 60204).

Danger!

When the “safe torque off” (STO) function is used, an

”emergency-off” according to EN 60204 is not possible without

additional measures. There is no electrical isolation, no service

switch or repair switch between motor and controller!
“Emergency-off” requires an electrical isolation, e.g. by a central

mains contactor!

After the installation is completed, the operator must check the wiring of the

safety function.
The functional test must be repeated at regular intervals. The time intervals

to be selected depend on the application, the entire system and the

corresponding risk analysis. The inspection interval should not exceed one

year.