2 error states, Error states, Safety engineering – Lenze E94AYAD - SM300 User Manual

Page 25

Advertising
background image

Safety engineering

Safety functions

Error states

1

1.3

1.3.2

1.3-3

EDS94AYAD EN 2.2

1.3.2

Error states

Detected errors or maloperationof the drive are assigned to error states with

definite reactions. The reaction can be co-ordinated with the complete drive

via the error states.

Features

Error status

System error

Error

Trouble

Event

Fatal internal error

Error

Monitoring function

LED ”ME”

On

Blinking

Flashing

Status of safety

module

Lockout (CPU stopped) Error status

Normal operation

The control category

according to EN 954-1

...

... has been

abandoned

... has been

abandoned

... has not been

abandoned

Reaction

The motor

immediately switches

to torque-free

operation via

z

STO

The motor is stopped via

z

STO or

z

SS1

Confirmation after

deactivated event

z

Connection and

disconnection of

the 24-V supply at

the safety module

z

Pulse at AIE

(0.3 s < t < 10 s)

z

via PROFIsafe

z

Connection and

disconnection of

the 24-V supply at

the safety module

z

Pulse at AIE

(0.3 s < t < 10 s)

z

via PROFIsafe

Response to the

confirmation

z

The module is reset.

z

The PROFIsafe communication is

interrupted.

z

The module is not

reset.

z

The PROFIsafe

communication is

not interrupted.

Tab. 1.3-2

Overview of error states

If errors occur in the PROFIsafe communication, the data is deactivated from

the PROFIsafe driver. The STO function is activated.
After the PROFIsafe communication is reinitialised, the drive is

automatically enabled again if no standstill function is selected.

Note!

If the system error also occurs after switching the 24-V supply,

please contact the service.