Safety engineering
Safety functions
Safe PROFIsafe connection
1
1.3
1.3.5
1.3-16
EDS94AYAD EN 2.2
Error number
Description
64
The Profisafe target address set does not comply with the parameter
F_Dest_Add.
65
The F_Dest_Add parameter has the invalid value 0x0000 or 0xFFFF.
66
The F_Source_Add parameter has the invalid value 0x0000 or 0xFFFF.
67
The F_WD_Time parameter has the invalid value 0 ms.
68
The F_SIL parameter does not have the valid value 0 ... 2.
69
The F_CRC_Length parameter does not have the valid value 2.
70
The version of the PROFIsafe parameter set is wrong.
71
CRC1 error
Tab. 1.3-17 Information contents of byte 11
The GSE file contains all information on the configuration of the PROFIBUS
system. This makes the integration easy and user-friendly.
Tip!
You will find the current GSE file for this Lenze product in the
Internet in the ”Downloads” area under
http://www.Lenze.com
Diagnostic information
GSE file