Safety engineering

Safety functions

Safe PROFIsafe connection

1

1.3

1.3.5

1.3-16

EDS94AYAD EN 2.2

Error number

Description

64

The Profisafe target address set does not comply with the parameter

F_Dest_Add.

65

The F_Dest_Add parameter has the invalid value 0x0000 or 0xFFFF.

66

The F_Source_Add parameter has the invalid value 0x0000 or 0xFFFF.

67

The F_WD_Time parameter has the invalid value 0 ms.

68

The F_SIL parameter does not have the valid value 0 ... 2.

69

The F_CRC_Length parameter does not have the valid value 2.

70

The version of the PROFIsafe parameter set is wrong.

71

CRC1 error

Tab. 1.3-17 Information contents of byte 11

The GSE file contains all information on the configuration of the PROFIBUS

system. This makes the integration easy and user-friendly.

Tip!

You will find the current GSE file for this Lenze product in the

Internet in the ”Downloads” area under
http://www.Lenze.com

Diagnostic information

GSE file