4 connection of safety sensors, Connection of safety sensors, Safety engineering – Lenze E94AYAD - SM300 User Manual

Page 18

Advertising
background image

Safety engineering

Device modules

Connection of safety sensors

1

1.2

1.2.4

1.2-8

EDS94AYAD EN 2.2

1.2.4

Connection of safety sensors

1.2.4.1

General

The following applies to the sensors of the SM300, version VA 1.xx:
ƒ Sensor type and function cannot be parameterised.
ƒ The sensor signals are converted into PROFIsafe bit information and

transmitted to the master control for processing. A local evaluation is

not carried out.

ƒ Unused sensor inputs must not be connected. The PROFIsafe bit of a

non-connected input is in the OFF state.

Note!

Make sure that an internal contact function test is carried out at

the safe inputs:
Safe input in the ON state

ƒ

A LOW level at one channel puts the input in the OFF state.

The discrepancy monitoring starts simultaneously.

ƒ

A LOW level must be detected at both channels within the

discrepancy time, otherwise a discrepancy error will be

reported.

ƒ

To be able to confirm the discrepancy error, a LOW level must

be detected before at both channels.

Safe input in the OFF state

ƒ

A HIGH level at one channel starts the discrepancy monitoring.

ƒ

A HIGH level must be detected at both channels within the

discrepancy time, otherwise a discrepancy error will be

reported.

ƒ

To be able to confirm the discrepancy error, a HIGH level must

be detected before at both channels.