3 safety functions, Safety functions, Integration into the application of the controller – Lenze E94AYAD - SM300 User Manual

Page 23: Safety engineering

Advertising
background image

Safety engineering

Safety functions

Integration into the application of the controller

1

1.3

1.3.1

1.3-1

EDS94AYAD EN 2.2

1.3

Safety functions

1.3.1

Integration into the application of the controller

For the use of the functions, certain settings in the controller are required.

Here, the Lenze PC software »Engineer« supports and guides you.
When a safety function is required, the safety technology activates the

corresponding safe monitoring function. However, the standstill function is

only directly executed with the ”safe torque off” (STO) function. Other safety

functions in which a controller action is required will need to be safely

monitored.
The actions of the drive (e.g. braking, braking to standstill, keeping the

standstill position) must be implemented in the basic device.
Depending on the design of the basic device, the user applications are

created by means of programming according to IEC 61131 or parameter

setting. For this purpose the system block InterfaceSafetyModule or the

control word SM_dwControl must be implemented into the control

configuration of the controller.
The connection to a user application serves to achieve the following:
1. Activation of the safety function in the safety module, e.g. SS1  the

monitoring starts.

2. The safety module transmits the information to the basic device that

the function has been activated using the corresponding bit in the

control word SM_dwControl.

3. The application must evaluate the control word and start the motion

sequence, e.g. braking etc.

Safety module and basic device communicate via an internal interface.
The request for a safety function is contained within the control word, the

information of which must be processed by the application.

Informatio

n

Offset

Bit

Byte

7

6

5

4

3

2

1

0

SM_

dwControl

4

SDIp

-

-

-

-

-

SS1

STO

5

-

-

-

-

-

-

-

SDIn

6

-

-

-

-

-

-

-

-

7

-

-

-

-

-

-

-

-

SM_

wState

8

-

-

-

EC_S1

EC_S0

-

-

STO

9

-

-

-

-

-

-

-

-

SM_wIo_

State

10

-

AIE

-

-

SD-In4

-

SD-In2 SD-In1

11

-

-

-

-

-

-

-

-

Tab. 1.3-1

Communication telegram from the safety module to the basic device.

Internal communication

Advertising