Safety engineering

Device modules

Connection of safety sensors

1

1.2

1.2.4

1.2-10

EDS94AYAD EN 2.2

1.2.4.2

Connection of passive sensors

The safe sensor inputs I1A, I1B and I2A, I2B are only suitable for equivalent

switching passive sensors.
To monitor passive sensors according to EN 954-1, cat. 3, the clock outputs

CLA and CLB must be wired. Please observe the following:
ƒ The clock outputs are only suitable for monitoring the passive sensors.
ƒ Always connect ...

– ... CLA with the A channel of the sensor input via the sensor.
– ... CLB with the B channel of the sensor input via the sensor.
– ... GCL with GIx of the sensor input.

ƒ The sensor inputs are tested cyclically through short LOW operation.
These errors are detected:
ƒ Short circuit to supply voltage.
ƒ Short circuit between the input signals when different clock outputs

are used.

ƒ Non-equivalent input signals after the discrepancy time.
These errors are not detected:
ƒ Short circuit between the input signals when the same clock outputs

are used.

Avoid unrecognisable errors by the installation, e.g. by separated cable

routing.

GCL

GI2

I2B

I2A

GCL

GI1

I1A

I1B

CLB

CLA

S1

S2

V

CC

ы

ы

SM300

E94AYAD

SSP94SM351

Fig. 1.2-4

Ways to detect errors

8

Unrecognisable errors