Safety engineering

Safety functions

Safe stop 1

1

1.3

1.3.4

1.3-8

EDS94AYAD EN 2.2

1.3.4.2

Conditions

Condition for using the function:
ƒ The basic device must be equipped with a communication module

E94AYCPM (PROFIBUS-DP), SW version 0.9 and connected to the

PROFIBUS.

ƒ The basic device must receive PROFIBUS data telegrams from a master

controller.

Danger!

If the request for the safety function is cancelled, the drive will

restart automatically.
You must provide external measures which ensure that the drive

only restarts after a confirmation (EN 60204).

1.3.4.3

Settings

This function does not have any parameters to be set.
Permanently set parameters:
ƒ The stopping time amounts to t

s

= 30 s.

Tip!

In many applications the stopping time is < 30 s. Thus STO is

already activated and the SS1 function is stopped when ”0”

speed is reached.
In order to determine the maximum response time consider the

stopping time (30 s).
This time can only be reduced by setting the STO function

through the safe control after the application-specific stopping

time.

1.3.4.4

Activation

How to activate the function:
ƒ A PROFIBUS data telegram with corresponding PROFIsafe contents is

transmitted to the basic device ( 1.3-12).