Page 69: Ȧȣ ȥ, Safety instructions, Thermal motor monitoring parameter setting, Calculating the release time

Advertising
background image

Safety instructions

Thermal motor monitoring

Parameter setting

2

l

69

EDKVF9383 DE/EN/FR 4.0

2.2.2

Parameter setting

Parameter setting

Code

Meaning

Value range

Lenze setting

C0066

Display of the I

2

xt utilisation of the motor

0 ... 250 %

C0120

Threshold: Triggering of an "OC6" error

0 ... 120 %

0 %

C0127

Threshold: Triggering of an "OC8" error

0 ... 120 %

0 %

C0128

Thermal time constant of the motor

0.1 ... 50.0 min

5.0 min

C0606

Response to "OC8" error

Trip, warning, off

Warning

Calculating the release time

t

+ * (C0128) @ ln

ȧ

ȡ
Ȣ

1

*

y

) 1

ǒ

IM

Ir

Ǔ

2

@ 100

ȧ

ȣ
Ȥ

I

M

Actual motor current

I

r

Rated motor current

y

C0120 or C0127

ƒ

The thermal capacity of the motor is expressed by the thermal motor time factor
(C0128). Please see the rated data of the motor for the value or ask the
manufacturer of the motor.

Reading the release time off the diagram

Diagram for the determination of the release times of a motor with a thermal motor time
factor of 5 min:

I

= 3 × I

mot

r

0

50

100

120

0

100

200

300

400

500

600

700

800

900

1000

t [s]

I t [%]

2

I

= 2 × I

mot

r

I

= 1.5 × I

mot

r

I

= 1 × I

mot

r

9300std105

Fig. 2−1

I

2

× t−monitoring: Release times for different motor currents and trigger thresholds

Imot

Motor current

I

r

Rated motor current

I

2

t

I

2

t load

T

Time

Advertising