With function "Safe torque off" active

5

l

97

EDKVF9383 DE/EN/FR 4.0

5.6.2

With function "Safe torque off" active

(from hardware version 1x)

Safety instructions for the installation of the "Safe torque off" function

ƒ

The installation and commissioning of the Safe torque off" function must be
carried out by skilled personnel only.

ƒ

All safety−relevant cables (e.g. control cable for the safety relay, feedback contact)
outside the control cabinet must be protected, for instance by a cable duct. Short
circuits between the single cables must be ruled out!

ƒ

Wiring of the safety relay K

SR

with insulated wire end ferrules or rigid cables is

absolutely vital.

ƒ

The electrical reference point for the coil of the safety relay K

SR

must be connected

with the protective conductor system (DIN EN 60204−1 paragraph 9.4.3). Only this
measure guarantees that the operation is protected against earth faults.