Technical data

General data and operating conditions

3

l

72

EDKVF9383 DE/EN/FR 4.0

Operating conditions

Ambient conditions

Climatic

Storage

IEC/EN 60721−3−1

1K3 (−20 ... +60 °C)

< 6 months

1K3 (−20 ... +40 °C)

> 6 months
> 2 years: form DC bus
capacitors

Transport

IEC/EN 60721−3−2

2K3 (−25 ... +70 °C)

Operation

IEC/EN 60721−3−3

3K3 (0 ... +50 °C)
> +40 °C: reduce the rated output current by 2.5 %/°C.

Pollution

EN 61800−5−1

Degree of pollution 2

Site altitude

< 4000 m amsl
> 1000 m amsl: reduce the rated output current by
5 %/ 1000 m.

Internal fan

975 m

3

/h volume flow per device

Mechanical

Vibration resistance

EN 61800−5−1

Electrical

Mains connection

Power system

TT, TN
(with earthed
neutral)

Operation is permitted without restrictions.

DC−bus operation

Possible for the variants V210, V240, V270, V300

Motor connection

Length of the motor
cable

At rated mains voltage and a switching frequency of

£ 2 kHz

without additional output filter.
For compliance with EMC regulations, the permissible cable
lengths may change.

shielded

100 m

unshielded

200 m

Mounting conditions

Mounting place

In the control cabinet

Mounting position

Vertical

Free spaces
Dimensions
Weights

^ 77