Electrical installation, Stop, Both, the master and the slave must be supplied – Lenze EVF9383 User Manual

Page 86

Advertising
background image

Electrical installation

Controller mains connection for a mains voltage of 400 V
Final works

5

l

86

EDKVF9383 DE/EN/FR 4.0

5.3

Controller mains connection for a mains voltage of 400 V

(

Stop!

The user is responsible for sufficient strain relief!

ƒ

Both, the master and the slave must be supplied!

BR2

BR2

BR1

BR1

PE

PE

U

U

V

V

W

W

L1

L1

L2

L2

L3

L3

PE

PE

L1, L2,

L3

L1, L2,

L3

25-30 Nm

25-30 Nm

M8

M8

221-264 lb-in

221-264 lb-in

PE

PE

15-20 Nm

15-20 Nm

M6

M6

133-176 lb-in

133-176 lb-in

40 mm

40 mm

0

1

9300VEC013

Fig. 5−7

Mains connection example

BR1, BR2

Brake resistor can only be operated with the variants V060 and V110
For connection see System Manual of 9300 vector

0

Master terminals

1

Slave terminals

Fuses and cable cross−sections for the mains supply

Master

Slave

Master

Slave

Master

Slave

EVF9381−EV
EVF9381−EVVxxx

315

315

150

2 Ч 50

1)

150

2 Ч 50

1)

95

95

EVF9382−EV
EVF9382−EVVxxx

315

315

150

2 Ч 50

1)

150

2 Ч 50

1)

95

95

EVF9383−EV
EVF9383−EVVxxx

400

400

240

2 Ч 95

1)

240

2 Ч 95

1)

150

150

1)

Multiple conductor; both conductors must have the same cross−section

2)

Lenze recommends to use fuses of the gRL utilisation category

Observe the national and regional legislation

5.4

Supply and fan connection at the controller for a mains voltage of 400 V/500V

(

Stop!

The user is responsible for sufficient strain relief!