Electrical installation

Installation according to EMC (installation of a CE−typical drive system)

5

l

80

EDKVF9383 DE/EN/FR 4.0

5

Electrical installation

(

Stop!

The drive controller contains electrostatically sensitive components.
The personnel must be free of electrostatic charge when carrying out assembly
and service operations.

5.1

Installation according to EMC (installation of a CE−typical drive system)

ƒ

Always separate motor cables from mains cables and control cables.

ƒ

Cross the motor cable at right angles with mains cables and control cables.

ƒ

Ideally the motor cable should be installed without interruptions.

ƒ

Connect all components (controller, choke) to a central earthing point (PE rail).

ƒ

Always connect the shields to the mounting plate with a contact surface as large as
possible or use the shield connections on the device side.

ƒ

Always connect the motor cable shield to both sides − to the controller and to the
motor.

ƒ

The cables of the analog and digital inputs and outputs must be shielded. Short
(up to 200 mm), unshielded cables must always be twisted.

ƒ

The shield connections of the control cables must have a distance of at least 50 mm
to the shield connections of the motor and DC cables.

ƒ

Digital cables require a double−sided shield connection.

ƒ

Analog cables require a single−sided shield connection on the inverter side.