background image

Electrical installation

Master and slave connection

Installation of the DC−busbars

5

l

83

EDKVF9383 DE/EN/FR 4.0

5.2.3

Installation of the DC−busbars

DC+

DC-

1

2

3

0

4

4

5

5

6

6

7

8

0

1

2

3

4

8

5

6

7

4

5

6

9300VEC024

Fig. 5−3

Mounting of +DC/−DC busbars

How to mount the DC busbars

1. Mount +DC busbar

3 :

– Remove hexagon socket screws M8

0.

– Position the DC busbar in the master and the slave.
– Fasten the DC busbar in the master and the slave with 1 hexagon socket screw

M8 × 45 mm

0, 1 plain washer 1 and 1 distance sleeve 2 each.

– Tighten the hexagon socket screws

0 (tightening torque: 10.9 Nm).

2. Mount −DC busbar

7 :

– Remove hexagon socket screws M8

4.

– Put both connecting cables

8 aside.

– Position the DC busbar in the master and the slave.
– Insert 2 hexagon socket screws M8 × 45 mm

4 each with plain washers 5 into the

bore holes of the DC busbar, finally passing them through the distance sleeves

6.

– Screw the hexagon socket screws

4 into the threaded holes in the master and

slave.

– Lay the connecting cable

8 in the master and slave with cable lug between the

busbar

7 and plain washer 5.

– Tighten the hexagon socket screws

4 (tightening torque: 10.9 Nm).