Electrical installation

Motor connection
Wiring of motor temperature monitoring

5

l

94

EDKVF9383 DE/EN/FR 4.0

Connection to the terminals T1, T2

(

Stop!

ƒ

Do not connect an external voltage to the terminals T1, T2. The controller
will be damaged.

ƒ

Do not use the terminals T1, T2 for safety−relevant wiring. Fault messages
via this input are only processed after 2 s.

Terminals T1, T2 at the controller

Input circuit for T1, T2

T1 T2

MONIT-OH8

T2

T1

15 V

93xx

J

3.3 k

7.4 k

2.7 k

9300STD328

9300VEC017

Fig. 5−14

Connection to the terminals T1, T2

T1, T2

Connection of PTC thermistor or thermal contact (NC contact)