Electrical installation, Stop – Lenze EVF9383 User Manual

Page 96

Advertising
background image

Electrical installation

Control terminals
Important notes

5

l

96

EDKVF9383 DE/EN/FR 4.0

How to connect the shield

3

1

0

2

9300vec063

Fig. 5−15

Connection of the cable shield with shield clip and strain relief with cable binder

0 Shield sheet

1 Fasten shield sheet with two screws M4 × 12 mm at the bottom of the control card

2 Connect cable shield with shield clip to the shield sheet

3 Provide a strain relief of the control cable at the shield sheet by means of a cable binder

Terminal data

(

Stop!

ƒ

Connect or disconnect the terminal strips only if the controller is
disconnected from the mains!

ƒ

Wire the terminal strips before connecting them!

ƒ

Unused terminal strips must also be plugged on to protect the contacts.

Cable type

Wire end ferrule

Maximum cable
cross−section

Tightening torque Stripping

length

Rigid

2.5 mm

2

(AWG 14)

0.5 ... 0.6 Nm

(4.4 ... 5.3 lb−in)

5 mm

Flexible

Without wire end
ferrule

2.5 mm

2

(AWG 14)

Flexible

Wire end ferrule
without plastic sleeve

2.5 mm

2

(AWG 14)

Flexible

Wire end ferrule with
plastic sleeve

2.5 mm

2

(AWG 14)