2 connection to the dc bus (+ug, -ug), 3 fan connection, Connection to the dc bus (+ug, −ug) – Lenze EVF9383 User Manual

Page 88: Fan connection, Electrical installation, 2 connection to the dc bus (+u, Both, the master and the slave must be supplied, Connect the fan to the master and the slave

Advertising
background image

Electrical installation

Supply and fan connection at the controller for a mains voltage of 400 V/500V
Connection to the DC bus (+UG, −UG)

5

l

88

EDKVF9383 DE/EN/FR 4.0

5.4.2

Connection to the DC bus (+U

G

, −U

G

)

ƒ

For compliance with EMC requirements, Lenze recommends to use shielded DC−bus
cables.

ƒ

Shield clamps are not included in the scope of supply.

ƒ

Both, the master and the slave must be supplied!

BR2

BR2

BR1

BR1

+UG

+UG

-UG

-UG

PE

PE

U

U

V

V

W

W

L1

L1

101

101

102

102

103

103

104

104

L2

L2

L3

L3

PE

PE

40 mm

40 mm

PE

15-20 Nm

M6

133-176 lb-in

PE

15-20 Nm

M6

133-176 lb-in

+U

G

+U

G

-U

G

-U

G

25-30 Nm

25-30 Nm

M8

M8

221-264 lb-in

221-264 lb-in

max.

300 mm

max.

300 mm

3

3

2

2

0

1

9300VEC083

Fig. 5−9

Connection example to +U

G

and −U

G

BR1, BR2

Brake resistor can only be operated with the variants V270 and V300
For connection see System Manual of 9300 vector

0

Master terminals

1

Slave terminals

2

Connect the DC−bus cable shield with a surface as large as possible to the control
cabinet mounting plate by using the clamps.

3

Conductive surface

Ensure to have the poles right!

Fuses and cable cross−sections for DC−bus connection

Master

Slave

Master

Slave

Master

Slave

EVF9381−EVV2xx
EVF9381−EVV300

350

350

150

2 Ч 50

1)

150

2 Ч 50

1)

95

95

EVF9382−EVV2xx
EVF9382−EVV300

400

400

240

2 Ч 95

1)

240

2 Ч 95

1)

95

95

EVF9383−EVV2xx
EVF9383−EVV300

500

500

240

2 Ч 95

1)

240

2 Ч 95

1)

150

150

1)

Multiple conductor; both conductors must have the same cross−section

2)

Only use fuses of the gRL utilisation category

Observe the national and regional legislation

5.4.3

Fan connection

)

Note!

Connect the fan to the master and the slave.

Advertising
This manual is related to the following products: