1 mains connection, Mains connection, Electrical installation – Lenze EVF9383 User Manual

Page 87: Both, the master and the slave must be supplied

Advertising
background image

Electrical installation

Supply and fan connection at the controller for a mains voltage of 400 V/500V

Mains connection

5

l

87

EDKVF9383 DE/EN/FR 4.0

5.4.1

Mains connection

ƒ

Both, the master and the slave must be supplied!

BR2

BR2

BR1

BR1

+UG

+UG

-UG

-UG

PE

PE

U

U

V

V

W

W

L1

L1

101

101

102

102

103

103

104

104

L2

L2

L3

L3

PE

PE

L1, L2,

L3

25-30 Nm

M8

221-264 lb-in

L1, L2,

L3

25-30 Nm

M8

221-264 lb-in

PE

15-20 Nm

M6

133-176 lb-in

PE

15-20 Nm

M6

133-176 lb-in

40 mm

40 mm

0

1

9300VEC035

Fig. 5−8

Mains connection example

BR1, BR2

Brake resistor can only be operated with the variants V270 and V300
For connection see System Manual of 9300 vector

0

Master terminals

1

Slave terminals

Fuses and cable cross−sections for the mains supply

Type

Installation to EN 60204−1

Fuse

2)

L1, L2, L3 [mm

2

]

PE [mm

2

]

Master

Slave

Master

Slave

Master

Slave

EVF9381−EVV210
EVF9381−EVV240
EVF9381−EVV270
EVF9381−EVV300

315A

315A

150

2 Ч 50

1)

150

2 Ч 50

1)

95

95

EVF9382−EVV210
EVF9382−EVV240
EVF9382−EVV270
EVF9382−EVV300

315A

315A

150

2 Ч 50

1)

150

2 Ч 50

1)

95

95

EVF9383−EVV210
EVF9383−EVV240
EVF9383−EVV270
EVF9383−EVV300

400 A

400 A

240

2 Ч 95

1)

240

2 Ч 95

1)

150

150

1)

Multiple conductor; both conductors must have the same cross−section

2)

Lenze recommends to use fuses of the gRL utilisation category

Observe the national and regional legislation