13435744_EDBMH01_v13

13

5

MCH RATINGS

The three tables in this section provide the input and output ratings of the MCH Series

drive. The tables are divided by Series Number: MH200, MH400 and MH500.

NOTE

The output current ratings are based on operation at carrier

frequencies of 8kHz and below.
At full ambient temperature, operation at carrier frequencies above

8 kHz require derating the drive by multiplying the output current

rating by the following factors: 0.94 at 10kHz, 0.89 at 12kHz, and

0.83 at 14kHz.
For more information, refer to Parameter 23 - CARRIER FREQ in

Section 18 - DESCRIPTION OF PARAMETERS.

MH200 SERIES RATINGS

MODEL

INPUT

OUTPUT

(200/240 Vac, 50 - 60 Hz)

(0 - 200/230 Vac)

MODEL

FOR MOTORS

NOMINAL

NOMINAL

NUMBER

RATED

INPUT CURRENT

POWER

CURRENT

POWER

(NOTE 1)

HP

kW

PHASE

(AMPS)

(KVA)

(AMPS)

(KVA)

MH210

1

0.75

3

5.5 / 4.8

2.0

4.6 / 4.0

1.6

MH220

2

1.5

3

9.3 / 8.1

3.4

7.8 / 6.8

2.7

MH230

3

2.2

3

13.0 / 11.3

4.7

11.0 / 9.6

3.8

MH250

5

3.7

3

20 / 17.7

7.4

17.5 / 15.2

6.1

MH275

7.5

5.5

3

30 / 26

10.6

25 / 22

8.8

MH2100

10

7.5

3

37 / 32

13.2

32 / 28

11.2

MH2150

15

11

3

55 / 48

19.8

48 / 42

16.7

MH2200

20

15

3

70 / 61

25.3

62 / 54

21.5

MH2250

25

18.5

3

89 / 77

32.0

78 / 68

27.1

MH2300

30

22

3

104 / 90

37.6

92 / 80

31.9

MH2400

3

40

30

3

99 / 99

41.0

104 / 104

41.4

MH2500

3

50

37.5

3

122 / 122

50.7

130 / 130

51.8

MH2600

3

60

45

3

145 / 145

60.5

154 / 154

61.3

NOTE 1: Refer to Section 3.0 for model number breakdown.

NOTE 2: Refer to Section 8.0 for recommended fuse type.

NOTE 3: For branch circuit protection, the 40HP, 50HP and 60HP 230V models must only

be installed with the appropriately rated UL Listed fuses.