ABOVE PRSET #3

ABOVE PRESET SPEED #3 - The relay energizes when the

output frequency exceeds the PRESET #3 value, and de-

energizes when the output frequency returns to a value lower

than the PRESET #3 value. Refer to Parameter 3 - PRESET #3

in Section 18.0 - DESCRIPTION OF PARAMETERS.

CURRENT LIMIT

The relay energizes when the drive is operating in current limit.

Once the current limit relay is energized, it remains energized

for a minimum of 500ms, regardless of whether the drive is still

in current limit. At the end of the 500ms interval, the relay will

de-energize if the drive is no longer in current limit. Refer to

Parameter 16 - CURRENT in Section 18.0 - DESCRIPTION OF

PARAMETERS.

AUTO/HAND SRC

The relay energizes when the drive speed is controlled by the

AUTO SOURCE, and de-energizes when the drive speed is

controlled by the HAND SOURCE. Refer to Section 14.2.4 -

SPEED REFERENCE SELECTION.

FOLLOWER PRES

FOLLOWER PRESENT - The relay energizes when the analog

input reference signal at TB-5B is greater than 2 mA, and de-

energizes if the signal falls below 2 mA.

MIN/MAX ALARM

The relay de-energizes when the feedback signal (in PID mode)

or the speed reference signal (in open-loop speed mode) is within

the limits set by MIN ALARM and MAX ALARM (Parameters

81 and 82), and energizes when the signal falls below the MIN

ALARM setting or exceeds the MAX ALARM setting.

INV MIN/MAX A

INVERSE MIN/MAX ALARM - The relay energizes when the

feedback signal (in PID mode) or the speed reference signal (in

open-loop speed mode) is within the limits set by MIN ALARM

and MAX ALARM (Parameters 81 and 82), and de-energizes

when the signal falls below the MIN ALARM setting or exceeds

the MAX ALARM setting.

MIN ALARM

The relay de-energizes when the feedback signal (in PID mode)

or the speed reference signal (in open-loop speed mode)

equals or exceeds the MIN ALARM setting (Parameter 81), and

energizes when the signal falls below the MIN ALARM setting.

INV MIN ALARM

INVERSE MIN ALARM - The relay energizes when the feedback

signal (in PID mode) or the speed reference signal (in open-

loop speed mode) equals or exceeds the MIN ALARM setting

(Parameter 81), and de-energizes when the signal falls below

the MIN ALARM setting.

MAX ALARM

The relay de-energizes when the feedback signal (in PID mode)

or the speed reference signal (in open-loop speed mode) is less

than or equal to the MAX ALARM setting (Parameter 82), and

energizes when the signal exceeds the MAX ALARM setting.

INV MAX ALARM

INVERSE MAX ALARM - The relay energizes when the feedback

signal (in PID mode) or the speed reference signal (in open-loop

speed mode) is less than or equal to the MAX ALARM setting

(Parameter 82), and de-energizes when the signal exceeds the

MAX ALARM setting.

RUN REVERSE

Energizes when the drive is running in reverse rotation, and de-

energizes when running in forward rotation.