79

A.2

BYPASS WIRING

MCH drives with the Bypass option do not have a terminal strip in the same location

as a "standard" MCH drive. There is a customer terminal strip located in the Bypass

compartment, eliminating the need to remove the drive cover. All customer wiring is

done in the bypass compartment. These terminals are briefly described below.

Contains two Form C relay outputs for status indication

(such as Run, Fault, At Speed, etc). The relays are rated

2 Amps at 120 Vac or 28 VDC.

Relay #1 is set using Parameter 54 - RELAY #1.

Relay #2 is set using Parameter 52 - TB14/RELAY #2.

Relay #3 is set using Parameter 53 - TB15/RELAY #3.

* A third relay is available as an option, and is included
with the optional 24 VDC power supply (see above).

Customer Start/Stop command between B3 and B4.

N.C. external interlocks between B1, B2, B3 (unit ships

with jumpers; remove jumpers to install interlocks).

Purge command between B1 and B5.

Remove jumper between B6 and B7 to disable bypass.

This terminal strip is at 120 Vac potential!

Essentially a duplicate of the MCH terminal strip. Refer to

Section 15.0 - MCH TERMINAL STRIP for a description

of the terminals.

Terminals 1, 12A, and 13C are used by the bypass and

cannot be used by the customer.

* A 24 VDC, 100 mA power supply is available as an

option. When the drive is equipped with this option, a

third Form C relay is provided (see below).

WARNING!

Do NOT connect 120VAC to this section

of the terminal strip! Severe damage to

the drive will result. This section of the

terminal strip is low voltage DC and

requires dry contacts.